KNX-GW2-RS232-RS485 Gateway KNX for RS232, REG 06, IP20
Description
The KNX-GW2-RS232-RS485 joins elements from the field of building automation with a variety of service and configuration connections of devices from entertainment technology. The programming depends on the individual application. Own Applications can be programmed, updated or exchanged via the USB interface.
The KNX-to-serial gateway is bidirectional. It receives data telegrams on the KNX bus and makes them available to the internal interface program, which generates serial telegrams from them. A KNX telegram can also be generated when a serial telegram arrives.
Depending ont he command length, approx. 1200 serial commands can be stored on the KNX-to-serial gateway. The group addresses user are defined together withe the command change to be sent in a project file and transferred via the USB interface. The physical address is set using the configurator.
Technical Details
Specification
Dimensions KNX-GW2-DMX: 107x75x31mm DIN Rail mounted housing (6TE)
Protection class: IP20
Ambient temperature: -5 °C .. 45 °C
Controls: 3x 16-step rotary switch
1x push button T1: 1x push button PRG and LED
USB-connector KNX-GW2-DMX: USB Type B
KNX-connector: KNX connecting terminal
Power supply: 20 .. 32VDC (approx. 150mW)
RS485-connector: 3 x Screw terminal 0.8mm2
Terminating resistor RS485: 120 Ohm (activated through a jumper)
Power supply: 9 .. 30VDC, 100mA, galvanically isolated intern, polarizesafe or USB
RS485: 250 kBaud, galvanically isolated
RS232: 115.2kBaud max
Properties
Properties
Technology | KNX |