Description
- ETS5 database with DCA (Device-Configuration-App) for synchronisation with KNX-Gate3 commissioning software
- Bi-directional telegram routing between KNX and RS232, RS485 or Ethernet
- Up to 500 freely definable strings for connection of devices with firm protocol
- Tracing of telegrams for diagnosis purposes
- Baud rate to the subsystem adjustable
- Transmission behaviour to the subsystem parameterisable
- KNX telegram rate limitation selectable
- Max. 2000 group addresses (resource-dependent)
Technical Details
Specification
TransmissionRate: 1.2...115.2 kbit/s
IP Communication: Ethernet 10/100
Rated voltage: C/DC24 V SELV
Mains frequency: 50 ... 60 Hz
Power consumption KNX: typ.150 mW
Degree of protection: IP20
Protection class: III
Ambient temperature: -5 ... +45 °C
Storage/transport temperature: -25 ... +70 °C
Fitting width (EB): 72mm ... 4 modules
Connection mode: Screw terminal
Weight: approx. 175 g
Single stranded: 0.5 ... 4 mm²
Finely stranded with conductor sleeve: 0.14...2.5 mm²
Finely stranded without conductor sleeve: 0.34...4 mm²
Commissioning mode: S-mode
Rated voltage KNX: DC21 ... 32 V SELV
Storage/transport temperature: -25 ... +70 °C
IP connection mode: RJ45 socket
IP transmission rate: 10 ... 100 Mbit/s
KNX medium: TP
Connection mode KNX: Standard KNX/EIB connection terminals
DMX connection: Screw terminal
RS232 connection: 9-pin D-sub socket
Properties
Properties
Technology | KNX |
Mounting | DIN Rail |
IP rating | IP20 |
Mounting Width | 4MW |