ZENNIO
ZCL-FC010V
MAXinBOX FC 0-10V VALVE. Fan coil controller for 2/4-pipe units with 0-10 VDC valve control signal
Product code:
ZCLFC010V
Controller for one 2-pipe or 4-pipe fan coil unit with 0-10V valves. Its 4 16A C-load outputs can be used to control the fan speed or as individual outputs. It has thermostat function and 4 analog-digital multifunction inputs that can be configured as binary inputs for sensors and potential-free push buttons, as temperature probe inputs or as motion sensor inputs. It includes a module with 10 logical functions and allows manual control of the outputs with status indication through LEDs.
Description
- 2 x 0-10VDC individual outputs for valve control.
- 4 individual outputs (suitable for capacitive loads, maximum 140µF) capable to control up to 4 fan speed.
- 4 analog/digital inputs.
- Manual output operation in 0-10VDC and individual outputs with push button and status indicator LED.
- Logical functions included.
- Output timing facilities.
- Total data saving on power failure.
- DIN rail unit assembly (EN 50022), with snap fit clamp.
- Size 67 x 90 x 80 mm (40.5 DIN units).
- KNX BCU integrated
- Possibility to connect different phases in adjoining outputs.
- CE directives compliant.
Technical Details
Specification
General System Specifications
- KNX Power Supply: 29VDC
- KNX Current Consumption: 11mA @ 29VDC
- Operating temperature: 0 ¡C to 55 ¡C
- Assembly: Independent control assembly device to be mounted inside of electrical panels with DIN rail (EN 50022).
- KNX bus failure response: Data saving
- Response when restarting KNX bus: Data recovering and output status change according to programming when recovering.
- Operation Indicator: Programming LED indicates programming mode (red) and test mode (green). Output status LED indicators show current output state.
Individual Output Specifications
- Contact type: Potential free outputs through bistable relays with tungsten pre-contact.
- Disconnection type: Micro-disconnection
- Rated current by output: 16A (6) 250V AC (4000 VA), 16A (6) 30V DC (480W)
- Maximum Power - Resistive load: 4000W
- Maximum Power - Inductive load: 1500VA
- Maximum inrush current: 800A/200_s, 165A/20ms
- Outputs per common (channel): 1 individual output.
- Different phase connection: Possibility to connect different phases in adjoining outputs
- Connection type: Terminal block (screw)
- Recommended cable section: 0.25 mm to 4 mm (26-10 AWG)
- Cable type: Stranded or solid wire
- Maximum response time: 50 ms
- Expected life - Mechanical: 3 million operations (60cpm)
- Expected life - Electrical: 100.000 cycles (6cpm/resistive load)
0-10V Output Specifications
- Output voltage: From 0 to 10VDC
- Output current: Maximum 10.5mA per output
- Outputs per common: 1
- Connection type: Terminal block (screw)
- Recommended cable section: 0.15 mm to 20.5 mm
- Cable type Stranded or solid wire
Input Specifications
- Number of inputs per common: 4
- Input voltage: +3.3V DC for the common
- Input current: 1.0mA @ 3.3V DC (each input)
- Input impedance: Approx. 3.3k ½
- Switching type: Dry voltage contacts between input and common
- Connection method: Cable screw terminal
- Max. cable length: 30 m.
- NTC probe length: 10.5 m. (max. 30m.)
- NTC accuracy (@ 25 ¡C): 0.5 ¡C
- Temperature measure precision: 0.1 ¡C
- Cable cross-section: 0.15 mm to 20.5 mm (26-12 AWG)
- Response time: Max 10ms.
Properties
Properties
Technology | KNX |
Mounting | DIN Rail |
Inputs | 4 |
Input voltage | KNX Bus (29VDC) |
Outputs | 6 |
IP rating | IP20 |
Mounting Width | 5MW |
Operating Voltage | KNX Bus (29VDC) |