Hitachi Air to Water to KNX Interface
The previous part number for this item was HI-AW-KNX-1
Description
FEATURES
- KNX certified.
- Configured by ETS standard configuration tool.
- Reduced dimensions allowing a quick installation inside the Air Conditioner unit.
- Offered all the required DPT objects to be compatible with all KNX thermostats in the market.
- Energy efficiency functions, such as ÒtimeoutÓ, Òopen windowÓ or ÒOccupancyÓ. Costs related to HVAC systems in a building are one of the highest and these functions allow to reduce them.
- Smooth integration of KNX thermostats allowing the control of the AC unit by the own temperature sensor of the thermostat.
- Simultaneous control of the AC unit by the IR remote controller and by KNX.
- Total control and monitoring of the AC unit from KNX, including AC unitÕs internal variables, running hours counter (for filter maintenance control) and error indication.
- Up to 5 scenes can be saved and executed from KNX.
DIRECT CONNECTION TO INDOOR UNITS
- The gateway is wired directly to an indoor unit. This allows not only the control of the main AC functions such as operating mode, fan speed, temperature setpoint, but the monitoring of errors, alarms and some internal variables.
EASY TO SET UP BY ETS
- The connection between the two networks is quickly set up in the ETS configuration tool using the product database available to download. Thanks to the high number of supported KNX DPTs and the KNX certification, the gateway ensures interoperability with any KNX device in the market.
Technical Details
Specification
Enclosure
- Plastic, type ABS (UL 94 V-0) de 2,5 mm thick
- Net dimensions (dxwxh): 71 x 71 x 27 mm / 2.8Ó x 2.8Ó x 1.1Ó
- Color: White RAL 9010
Weight: 70 g.
Power supply: Power is supplied by: 1 x KNX bus (29V DC, 6mA)
External Power Supply
- 10-40V DC, 100mA (Recommended: 12V DC, 100 mA)
- Must use a NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply.
- Plug-in terminal block for power connection (2 poles).
Terminal Wiring (for low-voltage signals)
- For terminal: solid wires or stranded wires (twisted or with ferrule)
- 1 core: 0.5mm2... 2.5mm2
- 2 cores: 0.5mm2... 1.5mm2
- 3 cores: not permitted
KNX port: 1 x KNX TP1 (EIB) port opto-isolated. Plug-in terminal block (2 poles). TNV-1
H-Link port: Plug-in terminal block for H-Link bus connection (2 poles) with no polarity
LED indicators: 1 x KNX programming.
Push buttons: 1 x KNX programming.
Configuration: Configuration with ETS
Operating Temperature: From -25oC to 60oC
Storage Temperature: From -40oC to 85oC
Isolation voltage: External Power Supply Ð KNX: 2500V. External Power Supply Ð H-Link: 1500V
RoHS conformity: Compliant with RoHS directive (2002/95/CE).
Certifications:
- CE conformity to EMC directive (2004/108/EC) and Low-voltage directive (2006/95/EC)
- EN 61000-6-2, EN 61000-6-3, EN 60950-1, EN 50491-3, EN 50090-2-2, EN 50428, EN 60669-1, EN 60669-2-1
Properties
Properties
Technology | KNX |
Mounting | Surface |
Input voltage | KNX Bus (29VDC) |
IP rating | IP20 |
Operating Voltage | KNX Bus (29VDC) |