Fujitsu AC interface with KNX, Serial and IP support - Up to 64 Indoor Units, 12 Outdoor Units
INTESIS IN775FGL00MO000

Fujitsu AC interface with KNX, Serial and IP support - Up to 64 Indoor Units, 12 Outdoor Units

Product code: IN775FGL00MO000
The Fujitsu Application has been specially designed to allow bidirectional control and monitoring of Fujitsu VRF systems from a BMS, SCADA, PLC or any other device working as a Modbus Master. The solution allows the integration of up to 64 indoor units from a single Interface.
Price (Excluding GST)
$P.O.A

Description

FEATURES

  • UL Listed.
  • Direct access to outdoor unit’s communication bus.
  • Scan: Automatic identification of the units presents on the VRF system.
  • Energy consumption signals from each indoor unit are available.
  • Outdoor unit’s signals available for the integration.
  • The interface is a Modbus slave able to manage Modbus TCP and Modbus RTU simultaneously.
  • Up to 6 TCP clients (incoming sockets) are supported.
  • Configuration through IP or USB (Console) port.
  • Easy integration with Intesis MAPS.
  • Automatic updates for both Intesis MAPS and interface’s firmware.


DIRECT CONNECTION TO VRF OUTDOOR UNITS

  • The gateway is directly connected to the outdoor units communication bus and enables the control of all the indoor units connected to the system. This allows not only the control and monitoring of the main AC functions but the access to some internal variables of the outdoor units.

SET UP BY INTESIS MAPS

  • The configuration is carried out using the Intesis¨ MAPS software. This one allows you to define your own settings for the device and offers extra functions available for all the new generation gateways. Thanks to the scan function, which allows to automatically discover all the units available in the installation, get the interface ready to work in a really short time.
  • Intesis MAPS makes it easy to identify any malfunction in the installations thanks to its robust diagnostic feature. 

Technical Details

Specification

Enclosure

  • Plastic, type PC (UL 94 V-0)
  • Net dimensions (dxwxh): 90x106x58 mm
  • Recommended space for installation (dxwxh): 130x115x100mm
  • Colour: Light Grey. RAL 7035

Mounting

  • Wall.
  • DIN rail EN60715 TH35.

Terminal Wiring (for power supply and low-voltage signals)

  • Per terminal: solid wires or stranded wires (twisted or with ferrule)
  • 1 core: 0.5mm2... 2.5mm2
  • 2 cores: 0.5mm2... 1.5mm2
  • 3 cores: not permitted

Power

  • 1 x Green pluggable terminal block (3 poles)
  • 12 to 36 VDC +/-10%, Max.: 250 mA
  • 24VAC +/-10% 50-60Hz, Max.: 127mA
  • Recommended: 24VDC

Ethernet

  • 1 x Ethernet 10/100 Mbps RJ45

Port EIA 485

  • 1 x Green pluggable terminal block (3 poles)
  • SGND (Reference ground or shield) 1500VDC isolation from other ports

Port KNX: 1 x Orange pluggable terminal block (2 poles): A, B

AC Ports

  • AC-Port A (serial, 2 poles): Not used
  • AC-Port B (serial, 3 poles): Not used
  • AC-Port C: (serial, 3 poles): AC bus connection (X1/X2)

LEDs

  • 2 x Run (Power/Error) 2 x Port EIA-485 TX/RX 2 x Port KNX TX/TR
  • 1 x Button indicator
  • 2 x Ethernet Link/Speed 2 x AC-Port A TX/RX
  • 2 x AC-Port B TX/RX
  • 2 x AC-Port C TX/RX

Binary inputs

  • 1 x Green pluggable terminal block (4 poles)
  • I1, I2, I3, and Common
  • 1500 VDC isolation from other ports

Console port: USB Mini-B type 2.0 compliant 1500 VDC isolation

SW A SW B

  • 2 x DIP switch blocks for EIA-485 serial port configuration:
  • Position 1:
  • On: 120 Ω termination active Off: 120 Ω termination inactive
  • Position 2 and 3:
  • On: Polarization active Off: Polarization inactive

Push button

  • 1 x Push button Factory reset
  • I-Am message (for BACnet only)
  • Normal mode/programming mode switch (for KNX only)

Operational temperature: Celsius: 0 .. 60°C Fahrenheit: 32 .. 140oF

Operational humidity: 5 to 95%. No condensation

Protection: IP20 (IEC60529)


Properties

Properties

Technology KNX
Mounting DIN Rail
IP rating IP20
Mounting Width 8MW
Operating Voltage 24VDC
Ivory Egg uses cookies to make your experience better and provide necessary site functionality. By using our website, you agree to set the cookies and accept the privacy policy