ZENNIO
ZCL-FC010F
MAXinBOX  FC 0-10V  FAN. Fan coil controller  for up to two 2/4-pipe units with 0-10 VDC fan speed control signal
Product code:
ZCLFC010F
Controller for up to two 2-pipe or 4-pipe fan-coil units with on/off valves and 0-10VDC fan speed control signal, ready to be mounted on DIN rails (4.5u). It has 4 multifunction outputs of 16A C-Load that can be used for the control of the fan-coil on/off valves or any other purpose. Moreover, it has 4 analog-digital multifunction inputs that can be configured as binary inputs for sensors and potential-free push buttons, as temperature probe inputs or as motion sensor inputs. It also includes 2 thermostats and 10 logical functions, and allows the manual control of all the outputs with status indication through LEDs.
  Description
- 2 x 0-10VDC individual outputs for fan control.
 - 4 individual outputs (suitable for capacitive loads, maximum 40µF).
 - 4 analog/digital inputs.
 - Manual output operation in 0-10VDC and individual outputs with push button and status indicator LED.
 - Logical functions included.
 - Output timing facilities.
 - Total data saving on power failure.
 - Size 67 x 90 x 80 mm (40.5 DIN units).
 - DIN rail unit assembly (EN 50022), with snap fit clamp.
 - KNX BCU integrated.
 - Possibility to connect different phases in adjoining outputs.
 - CE directives compliant.
 
Technical Details
Specification
General System Specifications
- KNX Power Supply: 29VDC
 - KNX Current Consumption: 11mA @ 29VDC
 - Operating temperature: 0 ¡C to 55 ¡C
 - Assembly: Independent control assembly device to be mounted inside of electrical panels with DIN rail (EN 50022).
 - KNX bus failure response: Data saving and output status change according to programming.
 - Response when restarting KNX bus: Data recovering and output status change according to programming when recovering.
 - Operation Indicator: Programming LED indicates programming mode (red) and test mode (green). Output status LED indicators show current output state.
 
Individual Output Specifications
- Contact type: Potential free outputs through bistable relays with tungsten pre-contact.
 - Disconnection type: Micro-disconnection
 - Rated current by output: 16A (6) 250V AC (4000 VA), 16A (6) 30V DC (480W)
 - Maximum Power - Resistive load: 4000W
 - Maximum Power - Inductive load: 2000VA
 - Maximum inrush current: 800A/200_s, 165A/20ms
 - Outputs per common (channel): 1 individual output.
 - Different phase connection: Possibility to connect different phases in adjoining outputs
 - Connection type: Terminal block (screw)
 - Recommended cable section: 0.25 mm to 4 mm (26-10 AWG)
 - Cable type: Stranded or solid wire
 - Maximum response time: 50 ms
 - Expected life - Mechanical: 3 million operations (60cpm)
 - Expected life - Electrical: 100.000 cycles (6cpm/resistive load)
 
0-10V Output Specifications
- Output voltage: From 0 to 10VDC
 - Output current: Maximum 10.5mA per output
 - Outputs per common: 1
 - Connection type: Terminal block (screw)
 - Recommended cable section: 0.15 mm to 20.5 mm
 - Cable type Stranded or solid wire
 
Input Specifications
- Number of inputs per common: 4
 - Input voltage: +3.3V DC for the common
 - Input current: 1.0mA @ 3.3V DC (each input)
 - Input impedance: Approx. 3.3k
 - Switching type: Dry voltage contacts between input and common
 - Connection method: Cable screw terminal
 - Max. cable length: 30 m.
 - NTC probe length: 10.5 m. (max. 30m.)
 - NTC accuracy (@ 25 ¡C): 0.5 ¡C
 - Temperature measure precision: 0.1 ¡C
 - Cable cross-section: 0.15 mm to 20.5 mm (26-12 AWG)
 - Response time: Max 10ms.
 
Properties
Properties
| Technology | KNX | 
| Mounting | DIN Rail | 
| Inputs | 4 | 
| Input voltage | KNX Bus (29VDC) | 
| Outputs | 6 | 
| IP rating | IP20 | 
| Mounting Width | 5MW | 
| Operating Voltage | KNX Bus (29VDC) | 