KNX Sensor Temperature Control VOC Concentration 4 Binary Inputs / Outputs - Round housing
ARCUS Neo-TC-VOC-ARE

KNX Sensor Temperature Control VOC Concentration 4 Binary Inputs / Outputs - Round housing

Product code: 30513663
The KNX-Sensor Neo-TC-VOC-ARE is used for measuring and controlling indoor air parameters
Price (Excluding GST)
$P.O.A

Description

  • Air temperature ( sensor in the housing ) also weighted with external temperature
  • VOC level ( volatile organic compound ) ( sensor in the housing )
  • Control functions for heating and cooling applications ( can be combined )
  • Setpoint temperatures for Comfort, Standby, Economy and Protection,
    selectable via KNX HVAC objects
  • Setpoint change via objects
  • Storage of minimum- and maximum-temperature
  • Heat- and frost-alarm
  • Limits for temperature
  • Fan control by VOC limits and external inputs
  • Adaptation for setpoint and maximum temperatures
  • Controller output 0...100% or programmable PWM for thermal actuators
  • Valve rinse function
  • Second temperature controller as auxiliary controller
    Four binary inputs / outputs ( floating )
  • Light control as switch / button with short, long, double and both function
  • Dimmer
  • Blind and shutter control
  • Programmable Encoder
  • Temperature adjustment
  • The binary inputs can be configured as outputs ( LED / Beeper )
    Four logic blocks for the logical link between internal and external signals.
  • 10 associated logic inputs / outputs
  • Heat- and cooling-request as additionally available signals
  • Functions "AND, OR, NOT, XOR" for binary logic
  • Functions "+ - *" for 8-bit values
  • Function "=" for conditional forwarding of events
    Applications
  • Detection and control of room temperature
  • Detection of VOC level
  • Decentralized control for steady KNX-valves or thermal actuators
  • Decentralized ventilation control depending on air quality
  • Evaluation of external switches and push buttons for switching functions

Technical Details

Specification

Measurement:        Temperature VOC Concentration
Control: integrated
Temperature Range: -25 .. +80C
Resolution: 0.02C
Accuracy: ± 0.4C (5..60C), sonst ± 0.8C
Measurement Range VOC 400 - 10000 ppm , CO2 equivalents
Binary In- / Output 4
Operating Voltage: KNX Bus Voltage 21 .. 32VDC
Power Consumption:        approx. 240mW ( at 24VDC )
Environment Temperature KNX-Module: Operating: -25 .. +80C Storage: -25 .. +80C
Environment Humidity KNX-Module: 10 .. 95% r.H Non Condensing
Bus Coupler: integrated
Auxiliary Supply: not required
Startup with the ETS Version 4 or higher: HLK305
Circuit Points:: KNX 2-pole clamps ( red / black )
Protection Class: IP20
Housing KNX-Module: Cover aluminum anodized ( black ) square: ( 80 x 80 x 6 ) mm round:  84 x 6 mm Standard flush-mounted socket ( 60/68 mm ) in the dry interior