KNX Sensor Temperature Humidity Control VOC Concentration 4 Binary Inputs / Outputs - Square housing
ARCUS Neo-THC-VOC-AQS

KNX Sensor Temperature Humidity Control VOC Concentration 4 Binary Inputs / Outputs - Square housing

Product code: 30533563
The KNX-Sensor Neo-THC-VOC-AQS is used for measuring and controlling indoor air parameters
Price (Excluding GST)
$P.O.A

Description

  • Air temperature ( sensor in the housing ) also weighted with external temperature
  • Humidity ( sensor in the housing )
  • VOC level ( volatile organic compound ) ( sensor in the housing )
  • Calculated values absolute humidity, dew point temperature and energy
    content ( enthalpy )
  • Control functions for heating and cooling applications ( can be combined )
  • Setpoint temperatures for Comfort, Standby, Economy and Protection,
    selectable via KNX HVAC objects
  • Setpoint change via objects
  • Storage of minimum- and maximum-temperature
  • Heat- and frost-alarm
  • Limits for temperature, humidity and VOC level
  • Fan control by humidity, VOC limits and external inputs
  • Detecting of dew point temperature and alarm / regulation at risk of
    condensation
  • Adaptation for setpoint and maximum temperatures
  • Controller output 0...100% or programmable PWM for thermal actuators
  • Valve rinse function
  • Second temperature controller as auxiliary controller
    Four binary inputs / outputs ( floating )
  • Light control as switch / button with short, long, double and both function
  • Dimmer
  • Blind and shutter control
  • Programmable Encoder
  • Temperature adjustment
  • The binary inputs can be configured as outputs ( LED / Beeper )
    Four logic blocks for the logical link between internal and external signals.
  • 10 associated logic inputs / outputs
  • Heat- and cooling-request as additionally available signals
  • Functions "AND, OR, NOT, XOR" for binary logic
  • Functions "+ - *" for 8-bit values
  • Function "=" for conditional forwarding of events
    Applications
  • Detection and control of room temperature and humidity
  • Detection of VOC level
  • Decentralized control for steady KNX-valves or thermal actuators
  • Decentralized ventilation control depending on humidity and air quality
  • Evaluation of external switches and push buttons for switching functions

Technical Details

Specification

Measurement:        Temperatur rel. Humidity VOC Concentration
Calculated Values: abs. Humidity Dewpoint Temperature Enthalpie
Control: integrated
Temperature Range: -25 .. +80C
Resolution: 0.02C
Accuracy: ± 0.4C (5..60C), sonst ± 0.8C
Humidity Range: 10 .. 95% r.H
Resolution: 0,02% r.H
Accuracy: ± 3% r.H (20..80%) at +20C, else ± 5% r.H
Measurement Range VOC 0 - 10000 ppm , CO2 equivalents
Binary In- / Output 4
Operating Voltage: KNX Bus Voltage 21 .. 32VDC
Power Consumption:        approx. 240mW ( at 24VDC )
Environment Temperature KNX-Module: Operating: -25 .. +80C Storage: -25 .. +80C
Environment Humidity KNX-Module: 10 .. 95% r.H Non Condensing
Bus Coupler: integrated
Auxiliary Supply: not required
Startup with the ETS Version 4 or higher: HLK305
Circuit Points:: KNX 2-pole clamps ( red / black )
Protection Class: IP20
Housing KNX-Module: Cover aluminum anodized ( black ) square: ( 80 x 80 x 6 ) mm round:  84 x 6 mm Standard flush-mounted socket ( 60/68 mm ) in the dry interior

Properties

Properties

Technology KNX
Ivory Egg uses cookies to make your experience better and provide necessary site functionality. By using our website, you agree to set the cookies and accept the privacy policy