KNX 8x16A Relay
Description
- LED switching status display for each channel
- Manual operation on device (even without bus connection)
- Adjustable characteristics: e.g. switching, delayed switching, pulse function
- Links, type of contact (NC contact/NO contact) and participation in central commands such as continuous On, continuous Off, central switching and save/call up scene
- Switching functions: On/Off, pulse, On/Off delay, staircase light with warning
- Logical links: e.g. lock, AND, release, OR
Technical Details
Specification
Operating voltage KNX: Bus voltage, ≤4 mA
Installation type: DIN rail
Width: 4 modules
Type of connection: KNX bus terminal
Max. cable cross section: Solid wire: 0.5 mm² (Ø 0.8) to 6 mm² | Stranded wire with end sleeve: 0.5 mm² to 4 mm²
Number of channels: 8
Type of contact: NO contact, 16 A, 3 A
Opening width: < 3 mm
Resistive load: 3680 W
Energy saving lamps: 300 W
LED lamp < 2 W: 55 W
LED lamp 2-8 W: 600 W
LED lamp > 8 W: 600 W
Inrush current: max. 800 A / 200 µs
Switching of various phases: Possible
C load: Yes
Type: Module FIX1
Ambient temperature: -5°C ... 45°C
Type of protection: IP 20
Protection class: II
Operating voltage: 110 – 240 V AC 50 – 60 Hz
Frequency: 50 – 60 Hz
Stand-by consumption: ~0.3 W
Incandescent/halogen lamp load: 2000 W
Fluorescent lamp load (conventional) parallel-corrected: 1300 W (140 µF)
Fluorescent lamp load (conventional) not corrected: 2000 VA
Fluorescent lamp load (electronic ballast): 1200 W
Voltage output: 240 V AC
Switching output: Potential-free
Suitable for SELV: Yes if all channels switch at SELV
Properties
Properties
Technology | KNX |
Outputs | 8 |
Mounting Width | 4MW |
EAN | 400346 8490990 |