HeatingBOX 230V 4X V2. Heating actuator for up to 4 outputs 230VAC and 4 inputs
  • Heatingbox 230v 4x v2 370x361
  • Heatingbox230v4x370x361
ZENNIO ZCL-4H230V2

HeatingBOX 230V 4X V2. Heating actuator for up to 4 outputs 230VAC and 4 inputs

Product code: ZCL4H230V2
Actuator for climate systems based on water pipes which allows the control of up to 4 outputs for on/off valves operated at 230 VAC by means of triacs with short-circuit protection. It includes one independent thermostat for each output, 4 analogue-digital inputs and a module with 10 logical functions. It has a sole power input for all the outputs, as well as a common neutral for an easier installation of the valves. It allows manual control of the outputs with status indication through LEDs.
Price (Excluding GST)
$P.O.A

Description

Features

  • 4 configurable outputs for 230 VAC valve control 
  • 4 thermostats
  • 4 analog/digital inputs
  • 10 logic functions
  • Manual control through buttons and LED status indicators Common 230 VAC input supply for all the outputs
  • Total data saving on KNX bus failure
  • Integrated KNX BCU (TP1-256)
  • Dimensions 67 x 90 x 36 mm (2 DIN units)
  • DIN rail mounting according to IEC 60715 TH35, with fixing clamp Conformity with the CE, UKCA, RCM directives (marks on the right side)

Zennio Thermostats:

Technical Details

Specification

KNX supply
Voltage (typical): 29 VDC SELV
Voltage range: 21-31 VDC
Maximum consumption 
29 VDC (typical): 7.9mA, 229.1mW
24 VDC: 10mA, 240mW
Connection type: Typical TP1 bus connector for 0.8 mm Ø rigid cable

External power supply: 230 V 50/60 Hz
Operation temperature: 0 .. +55 °C
Storage temperature: -20 .. +55 °C
Operation humidity: 5 .. 95%
Storage humidity: 5 .. 95%
Complementary characteristics: Class B
Protection class / Overvoltage category: II / III (4000 V)
Operation type: Continuous operation
Device action type: Type 1
Electrical stress period: Long
Degree of protection / Pollution degree: IP20 / 2 (clean environment)
Installation: Independent device to be mounted inside electrical panels with DIN rail (IEC 60715)
Minimum clearances: Not required
Response on KNX bus failure: Data saving according to parameterization
Response on KNX bus restart: Data recovery according to parameterization
Operation indicator: The programming LED indicates programming mode (red) and test mode (green). Each output LED indicates its status (fixed=active output; flashing=overload or short-circuit). The blue blinking of the programming LED indicates a 3 minutes lock due to the suffering of 4 short-circuits in less than 3 minutes.
Weight: 115 g
PCB CTI index: 175 V
Housing material / Ball pressure test temperature: PC FR V0 halogen free / 75 °C (housing) - 125 °C (connectors)

Properties

Properties

Technology KNX
Mounting DIN Rail
Outputs 4
HVAC support Regulation
IP rating IP20
Operating Voltage 230VAC

Documents & Downloads