IndustrialBOX 4. Industrial actuator with 4 outputs (20 A - 200 µF), mechanical manual operation and KNX Secure
  • Industrialbox 4 370x361
  • Industrialbox 4 2000x2000
ZENNIO ZIO-INB4

IndustrialBOX 4. Industrial actuator with 4 outputs (20 A - 200 µF), mechanical manual operation and KNX Secure

Product code: ZIOINB4
Actuator for DIN-rail (4 units) with 4 individual outputs with industrial relays (20 A C-Load). It allows manual control of its outputs through switches that directly control the relays, independently of the power supply. It includes 20 independent logical functions. It is compatible with KNX Secure.
Price (Excluding GST)
$P.O.A

Description

  • 4 individual outputs up to 20 A
  • Outputs suitable for capacitive loads, maximum 200 μF
  • Possibility of connecting different phases in adjacent outputs
  • Supports KNX Data Secure
  • 2 Master Light controls
  • Independent manual control for physical operation/actuation of the relay
  • 20 logic functions
  • Output timing
  • Total data saving on KNX bus failure
  • Integrated KNX BCU (TP1-256)
  • Dimensions 67 x 90 x 70 mm (4 DIN units)
  • DIN rail mounting according to IEC 60715 TH35, with fixing clamp
  • Conformity with the CE, UKCA, RCM directives (marks on the right side)

Technical Details

Specification

KNX supply:
Voltage (typical): 29 VDC SELV
Voltage range: 21-31 VDC
Maximum consumption Voltage: 29 VDC (typical) 4.0mA, 116.7mW. 24 VDC1 10mW, 240mW.
Connection type: Typical TP1 bus connector for 0.8 mm Ø rigid cable

External power supply:  Not required
Operation temperature: 0 .. +55 °C
Storage temperature: -20 .. +55 °C
Operation humidity: 5 .. 95%
Storage humidity: 5 .. 95%
Complementary characteristics: Class B
Protection class / Overvoltage category: II / III (4000 V)
Operation type: Continuous operation
Device action type: Type 1
Electrical stress period: Long
Degree of protection / Pollution degree: IP20 / 2 (clean environment)
Installation: Independent device to be mounted inside electrical panels with DIN rail (IEC 60715)
Minimum clearances: Not required
Response on KNX bus failure: Data saving according to parameterization
Response on KNX bus restart: Data recovery according to parameterization
Operation indicator: The programming LED indicates programming mode (red)

Weight: 334 g

PCB CTI index: 175 V
Housing material / Ball pressure test temperature: PC FR V0 halogen free / 75 °C (housing) - 125 °C (connectors)